Honeywell RM7800L1012 Programming Burner Control

Place of Origin china
Brand Name Honeywell
Certification CE
Model Number RM7800L1012
Minimum Order Quantity 1
Price USD$840
Packaging Details carton
Delivery Time in stock
Payment Terms L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability 500pc

Contact me for free samples and coupons.

Whatsapp:0086 18588475571

Wechat: 0086 18588475571

Skype: sales10@aixton.com

If you have any concern, we provide 24-hour online help.

x
Product Details
Application Programming Control Operating Conditions -40 F To 140 F
Early Spark Termination Yes, 5 Seconds Flame Establishing Period - Pilot 4 Sec Or 10 Sec
Highlight

Honeywell RM7800L1012 Programming Burner Control

,

Honeywell RM7800L1012

,

Honeywell RM7800L1012 Burner Control

Leave a Message
Product Description

Features

Functions Include Automatic Burner Sequencing, Flame Supervision, System Status Indication, System Or Self Diagnostics And Troubleshooting
Includes Keyboard Display Module
4 Second Or 10 Second Pilot Flame Establishing Period
Access For External Electrical Voltage Checks
Application Flexibility And Communication Interface Capability
Five LEDs Provide Sequence Information
Five Function Run/Test Switch
Interchangeable Plug-In Amplifiers
Local Or Remote Annunciation Of Operation And Fault Information (Optional)
Non-Volatile Memory Retains History Files And Lockout Status After Loss Of Power
Compatible With Existing Honeywell Flame Detectors

Technical Details

Application
Programming Control
Operating Conditions
-40 F To 140 F
Early Spark Termination
Yes, 5 Seconds
Flame Establishing Period - Pilot
4 sec or 10 sec
Flame Establishing Period - Main
10 sec or 15 sec

 

  • Manufacturer: Honeywell

  • RM7800L1012/U

  • Programmer Ctrl LHL-LF&HF Proven Purge

  • Functions include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and trouble shooting.

  • Access for external electrical voltage checks.

  • Application flexibility and communication interface capability.

  • Five LEDs provide sequence information.

  • Five function Run/Test Switch.

  • Interchangeable plug-in flame amplifiers.

  • Local or remote annunciation of operation and fault information (optional).

  • Nonvolatile memory retains history files and lockout status after loss of power.

  • Compatible with existing Honeywell flame detectors.

  • Includes Keyboard Display Module.

  • Application : Programming Control

  • Dimensions (in.) : 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase

  • Dimensions (mm) : 127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase

  • Weight (lb) : 1 lb 10 oz

  • Weight (kg) : 0.7 kg

  • Comments : Includes S7800 Display, LHL-LF&HF Proven

  • Frequency : 50 Hz; 60 Hz (±10%)

  • Voltage : 120 Vac (+10, -15%)

  • Shipping and Storage Temperature Range (F) : -40 F to +140 F

  • Shipping and Storage Temperature Range (C) : -40 C to +60 C

  • Flame Establishing Period - Pilot : 4 sec or 10 sec

  • Flame Establishing Period - Main : 10 sec or 15 sec

  • Interlocks : Lockout

  • Preignition : Yes

  • PrePurge : Determined by ST7800A Purge Timer Card

  • PostPurge : 15 sec

  • Early Spark Termination : Yes, 5 sec

  • Required Components : Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800A Plug-in Purge Timer Card.

  • AirFlow Check : User selectable

  • Second Stage Pilot Valve : Interrupted

  • Pilot Type : interrupted

  • Vibration : 0.5 G environment

  • Shipping Weight : 2 Kg